Sauna electrical requirements: circuit, breaker and wire
An electric sauna heater is one of the largest loads in a house. Nearly every traditional heater above about 2 kW needs its own 240 volt circuit, hardwired, with nothing else on it. The heater size decides everything else.
Amps, breaker and wire by heater size
| Heater | Draw at 240 V | With 125% | Breaker | Copper wire |
|---|---|---|---|---|
| 3 kW | 12.5 A | 15.6 A | 20 A | 12 AWG |
| 4.5 kW | 18.8 A | 23.4 A | 30 A | 10 AWG |
| 6 kW | 25.0 A | 31.3 A | 30 to 40 A | 10 AWG or 8 AWG |
| 8 kW | 33.3 A | 41.7 A | 40 to 50 A | 8 AWG |
| 9 kW | 37.5 A | 46.9 A | 50 A | 8 AWG or 6 AWG |
| 10.5 kW | 43.8 A | 54.7 A | 50 to 60 A | 6 AWG |
| 12 kW | 50.0 A | 62.5 A | 70 A | 4 AWG |
Breaker and wire columns are what heater makers publish for each size; the 12 kW row is worked out from the 125% rule.
Where the numbers come from
Amps are watts divided by volts. A 6 kW heater is 6,000 รท 240 = 25 amps.
The 125% figure is the allowance electrical codes make for a load that runs for long stretches. Electricians size the circuit from it.
Published breaker sizes vary. For a 6 kW heater one maker lists a 30 amp breaker and another lists 40. Each heater is tested and listed with the protection in its own manual, so the manual wins over any chart, including this one.
Things that change the job
- Distance from the panel. Runs over about 50 feet usually step up one wire size to limit voltage drop. An outdoor sauna across the yard also needs wiring rated for burial or conduit.
- Room in the panel. A 100 amp service that already feeds a range, a dryer and air conditioning may not have 40 or 50 amps spare. Your electrician checks this with a load calculation.
- Ground-fault protection. Rules differ by location and by heater. Some codes call for it on outdoor circuits while some heater makers advise against it. Your electrician and the manual settle it.
- 208 volt supplies. Some condos and commercial buildings have 208 volts. A heater rated at 240 volts gives about three quarters of its heat there, so the room needs the next size up.
- Controls and lighting. A separate control panel, lights or a fan may need a small 120 volt circuit as well.
Infrared cabins
Infrared saunas draw far less. One and two person cabins of about 1,400 to 1,800 watts plug into a 120 volt outlet, though a dedicated 20 amp circuit avoids tripped breakers. Larger cabins often need 240 volts.
What to give your electrician
- The heater model and its installation manual.
- The heater power in kW and the breaker size the manual states.
- The distance from the panel to the sauna, and whether the route is indoors or buried.
- Whether the control is built into the heater or mounted separately.
Permits and inspection are normally required for a new 240 volt circuit in both the United States and Canada.